General Information for Tripp Lite Power - PDU
Tripp Lite PDUMH20HVATNET 3.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C20 Inlets, 8 C13 & 2 C19 Outputs, 1U, TAA, Switched, 1U, Horizontal, Metal, Black, 10 AC outlet(s)
PDUMH20HVATNET 3.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C20 Inlets, 8 C13 & 2 C19 Outputs, 1U, TAA
Tripp Lite Switched Automatic Transfer Switch / ATS PDU provides a redundant power option for single-corded network devices. Dual input cords support separate connection to PRIMARY and SECONDARY power sources. The ATS will normally maintain continuous output to all outlets as derived from the primary input cable. If the primary power source becomes unstable or fails altogether, the ATS will switch over to the secondary power source until the primary input is restored and stable. Switched PDU features include individually controllable output receptacles and built-in network interface. Super-fast switchover between primary and secondary power sources occurs within milliseconds. ATS functionality is supported by any two compatible AC power sources, regardless of phase angle, to support a variety of advanced redundant power networking applications. Enables fault tolerant hot-swappable UPS protection when used with a single UPS and fully redundant UPS protection when each cord is connected to a separate UPS system.
In a two-UPS environment, the primary input cable must be supported by a full time sine wave UPS with zero transfer time. Tripp Lite SmartOnline series is highly recommended for use as the primary UPS in a two-UPS application. ATS configurations utilizing separate mains circuits, backup generators and even separate utility power grid feeds are fully supported. On-board ATS processor constantly evaluates power quality on both input sources to prevent transfer to the secondary source when unavailable or of lower quality than the primary source. Front input LED's display primary or secondary power availability. Built-in LX Platform network management interface card. The Java-free LX Platform HTML5-based network interface enables full remote access for PDU status monitoring and email notifications via secure web browser, SNMP, telnet or SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network. Optional EnviroSense2 modules (sold separate) provide a variety of environmental monitoring capabilities. Protocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP.
200-240V 20A Automatic Transfer Switch (ATS) / Switched PDU (Agency de-rated to 16A continuous)
Enables redundant A/B power option for single-corded network devices
2 digit display reports power consumption in amps
1U horizontal rackmount form factor
10 outlets (8 C13 switched / 2 C19 unswitched)
Set of Plug-lock output power cable retention sleeves prevent accidental disconnection of connected devices
Two C20 inlets for separate Primary and Secondary inputs; two 12 ft / 3.7m C20 input cables included
ATS circuits normally maintain output sourced from the primary input cable; As primary input power fails, the ATS will switch to maintain output sourced from the secondary input cable until power on the primary input is restored and stable
ATS configurations enable hot-swappable UPS protection when used with a single UPS and redundant UPS protection when each cord is connected to a separate UPS system (in a two-UPS environment, the primary input cable must be supported by an online UPS with zero transfer time)
Advanced ATS configurations utilizing separate mains circuits, backup generators and separate out of phase utility power grid feeds are supported
On-board ATS processor constantly evaluates power quality on both inputs to prevent transfer to the secondary source when unavailable or of lower quality than the primary source
2-7 millisecond transfer time
Switched outlets and ethernet interface supports individual outlet control on a real-time or programmable basis and user-specified alarm notification thresholds for all reported site power conditions
LX Platform interface allows full remote access for power monitoring with email notifications via secure web browser, SNMP, telnet or SSH
Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities
Outlets are factory programmed for sequential turn-on at 250 millisecond intervals when the PDU is first energized
LEDs confirm power availability on both input lines and for each output receptacle
Federal Trade Agreements Act / TAA Compliant for GSA Schedule purchases PDUMH20HVATNET 3.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C20 Inlets, 8 C13 & 2 C19 Outputs, 1U, TAA
Further details for this product, PDUMH20HVATNET 3.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C20 Inlets, 8 C13 & 2 C19 Outputs, 1U, TAA, can be found at the manufacturer website. Please note, these web addresse(s) are supplied by 3rd parties, Quzo UK is not responsible for the content.
3.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C20 Inlets, 8 C13 & 2 C19 Outputs, 1U, TAA
Tripp Lite PDUMH20HVATNET 3.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C20 Inlets, 8 C13 & 2 C19 Outputs, 1U, TAA. PDU types: Switched, Rack capacity: 1U, Mounting: Horizontal. AC outlets quantity: 10 AC outlet(s), AC outlet types: C13 coupler, C19 coupler, Power plug: C20 coupler. Cable length: 3.6 m, Certification: UL 60950 (USA, Canada), CE (Europe), Class A (Emissions), NOM (Mexico). Nominal input voltage: 200-240 V, Maximum current: 20 A, AC input frequency: 50 -
Warranty information: 2-year limited
Initial Release Date: 10/03/2011
Read more »
Tripp Lite PDUMH20HVATNET 3.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C20 Inlets, 8 C13 & 2 C19 Outputs, 1U, TAA PDUMH20HVATNET Specifications
Product Type
Power Distribution Unit
Product Type
Power - PDU
Collection Model Tripp Lite PDUMH20HVATNET 3.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C
Manufacturer Product Type
Tripp Lite Power - PDU
Product colour
Black
PDU types Switched
LED indicators Yes
Housing material Metal
Power plug C20 coupler
AC outlet types C13 coupler, C19 coupler
AC outlets quantity 10 AC outlet(s)
Maximum current 20 A
AC input frequency 50 - 60 Hz
Height 43.7 mm
Width 440.2 mm
Depth 375.2 mm
Dimensions (WxDxH) 439 x 376 x 44 mm
Weight 4.69 kg
Mounting Horizontal
Year 2011
Rack capacity 1U
Country of origin Taiwan
Storage temperature (T-T) -15 - 50 C
Operating altitude 0 - 3000 m
Certification UL 60950 (USA, Canada), CE (Europe), Class A (Emissions), NOM (Mexico)
Products per master (outer) case 1 pc(s)
Sustainability certificates RoHS
Compliance certificates RoHS
Package width 528.3 mm
Package depth 594.4 mm
Package height 137.2 mm
Package weight 7.71 kg
Cable Length 3.6 m
Nominal input voltage 200-240 V
Nominal output voltage 200-240 V
MPN PDUMH20HVATNET
| Manufacturer PDF Specifications |
| Manufacturer PDF Manual |
Tripp Lite PDUMH20HVATNET 3.8kW Single-Phase Switched Automatic Transfer Switch PDU, Two 200-240V C20 Inlets, 8 C13 & 2 C19 Outputs, 1U, TAA PDUMH20HVATNET Reviews
There are no reviews for this product.